Single-phase
S = V x I
P = S x PF
Q = √(S2 - P2)
Electrical calculator
Calculate kW, kVA, kVAR, and phase angle for single-phase or balanced three-phase AC circuits.
Instant AC power solver
Results update automatically. For three-phase systems, use line-to-line voltage and line current.
Calculated result
Formulas
S = V x I
P = S x PF
Q = √(S2 - P2)
S = √3 x V x I
P = √3 x V x I x PF
Q = √(S2 - P2)
Use volts and amps as base inputs. The calculator converts mV, kV, mA, and kA before solving, then reports power in kW, kVA, and kVAR.
Worked example
Suppose a balanced three-phase motor circuit uses 480 V line-to-line, draws 32 A, and has a 0.86 power factor.
S = sqrt(3) x 480 x 32
S = 26.60 kVA
P = 26.60 x 0.86
P = 22.88 kW
Q = sqrt(S2 - P2)
Q = 13.56 kVAR
This means the supply equipment must carry about 26.60 kVA, while the load converts about 22.88 kW into useful electrical input power. Mechanical shaft output would be lower after motor losses.
Guide
Reference
The usable power converted into work, heat, light, or mechanical output by the load.
The oscillating power associated with magnetic and electric fields in inductive or capacitive loads.
The total AC power capacity required from the source, transformer, generator, or distribution equipment.
The ratio of real power to apparent power. A higher value means the system uses supplied power more effectively.
Assumptions and limits
Useful next checks
After estimating current and power, verify conductor voltage drop for the circuit length and wire size.
Open voltage drop calculatorLow power factor can increase apparent power demand and current for the same useful kW load.
Open power factor calculatorUse current, voltage, phase arrangement, and allowable voltage drop when selecting conductors.
Open wire size calculatorFor resistive or DC-equivalent checks, calculate voltage, current, resistance, and power with Ohm's law.
Open Ohm's law calculatorFAQ
kW is real power, kVA is apparent power, and kVAR is reactive power. Together they describe the AC power triangle.
Yes, it is useful for estimating motor electrical input power when you know voltage, current, phase type, and power factor. It does not replace nameplate data, efficiency data, service factor, or code-based sizing.
The square-root-of-3 factor comes from the 120-degree phase separation in a balanced three-phase system when using line voltage and line current.
No. The result is electrical input power. Mechanical shaft output requires motor efficiency or measured output data.
Related
Calculate cutoff frequencies for RC and RL filter circuits.
Calculate inductance for air-core or magnetic-core coils.
Find voltage, current, resistance, or power using Ohm's law.
Estimate power factor and AC circuit efficiency.
Analyze impedance, phase angle, and resonance for common circuit types.
Tell us what would make EngLab more useful for your engineering work.